6 Parameterisation
BU 0200 GB
Subject to technical alterations
163
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P402
[-01]
...
[-06]
Analog input adjustment: 0%
S
-50.00 ... 50.00 V
{ all 0.00 }
[-01] =
Ext
ernal
analog in
put
1
, AIN1 of the first I/O extension (SK xU4-IOE).
[-02] =
Ext
ernal
analog in
put
2
, AIN1 of the first I/O extension (SK xU4-IOE).
[-03] =
Ext
ernal
a
nalog
i
nput
1 2nd IOE
, AIN1 of the second I/O extension
(SK xU4-IOE) (= analog input 3).
[-04] =
Ext
ernal
a
nalog
i
nput
2 2nd IOE
, AIN1 of the second I/O extension
(SK xU4-IOE) (= analog input 4).
[-05] =
reserved
[-06] =
reserved
... only with
SK CU4-IOE or
SK TU4-IOE
This parameter sets the voltage which should correspond with the minimum value of the
selected function for the analog input 1 or 2. In the factory setting (setpoint) this value is
equivalent to the setpoint set via P104 >Minimum frequency<.
Note:
Standardisation of typical signals such as 0(2)-10V or 0(4)-20mA is carried out via the DIP
switches on the I/O-extension module. An additional adjustment of parameters (P402) and
(P403) is not made in this case.
P403
[-
01]
...
[-
06]
Analog input adjustment: 100%
S
-50.00 ... 50.00 V
{ all 10.00 }
[-01] =
Ext
ernal
analog in
put
1
, AIN1 of the first I/O extension (SK xU4-IOE).
[-02] =
Ext
ernal
analog in
put
2
, AIN1 of the first I/O extension (SK xU4-IOE).
[-03] =
Ext
ernal
a
nalog
i
nput
1 2nd IOE
, AIN1 of the second I/O extension
(SK xU4-IOE) (= analog input 3).
[-04] =
Ext
ernal
a
nalog
i
nput
2 2nd IOE
, AIN1 of the second I/O extension
(SK xU4-IOE) (= analog input 4).
[-05] =
reserved
[-06] =
reserved
... only with
SK CU4-IOE or
SK TU4-IOE
This parameter sets the voltage which should correspond with the maximum value of the
selected function for the analog input 1 or 2. In the factory setting (setpoint) this value is
corresponds with the setpoint set via P105 >Maximum frequency<.
Note:
Standardisation of typical signals such as 0(2)-10V or 0(4)-20mA is carried out via the DIP
switches on the I/O-extension module. An additional adjustment of parameters (P402) and
(P403) is not made in this case.
Содержание SK 200E Series
Страница 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 54: ...NORDAC SK 200E Manual 54 Subject to technical alterations BU 0200 GB 2 9 5 EC declaration of conformity...
Страница 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Страница 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Страница 263: ...10 Keyword index BU 0200 GB 263...
Страница 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Страница 265: ...The Nordac SK 200E is available to order from www inverterdrive com...