NORDAC SK 200E Manual
226
Subject to technical alterations BU
0200
GB
Display in the
SimpleBox
Group
Details in
P700 [-02]
Warning
Text in the Parameter Box
Cause
Remedy
C004
4.1 Overcurrent
measurem
ent
Warning: Pulse switch-off is active
The limiting value for the activation of the pulse switch-off
(P537) has been reached (only possible if P112 and P536
are switched off)
FI is overloaded
Check motor data (P201 … P209)
12.1 Limit
moto
r
/Customer
Warning: 80% of the drive switch-off limit (P534 [-01]) has
been exceeded.
Reduce load on motor.
Set a higher value in (P534 [-01]).
12.2 Limit
gen
erator
Warning: 80% of the generator switch-off limit (P534 [-02])
has been exceeded.
Reduce load on motor.
Set a higher value in (P534 [-02]).
12.3
Torque limit
Warning: 80% of the limit from the potentiometer or the
setpoint source has been reached. P400 = 12
C012
12.4 Current
limit
Warning: 80% of the limit from the potentiometer or the
setpoint source has been reached. P400 = 14
Содержание SK 200E Series
Страница 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 54: ...NORDAC SK 200E Manual 54 Subject to technical alterations BU 0200 GB 2 9 5 EC declaration of conformity...
Страница 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Страница 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Страница 263: ...10 Keyword index BU 0200 GB 263...
Страница 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Страница 265: ...The Nordac SK 200E is available to order from www inverterdrive com...