5 Commissioning
BU 0200 GB
Subject to technical alterations
131
5.3 KTY84-130 connection
The current vector regulation of the SK 200E series can be further optimised by the use of a KTY84-130
temperature sensor (R
th(0°C)
=500
Ω
, R
th(100°C)
=1000
Ω
). By continuous measurement of the motor temperature,
the highest precision of regulation by the frequency inverter and the associated optimum speed precision of
the motor is achieved at all times. As the temperature measurement starts immediately after the (mains)
switch-on of the frequency inverter, the frequency inverter provides immediate optimum control, even if the
motor has a considerably increased temperature after an intermediate "Mains off / Mains on" of the
frequency inverter.
A KTY-84 sensor can only be connected to one of the two analog inputs of the I/O - extension module
(SK xU4-IOE).
Connection example
(Assignment of connections, Analog Input 2)
SK
CU4-IOE
SK
TU4-IOE
(Illustration shows a section of the terminal blocks)
Parameter settings (Analog Input 2)
For the function of the KTY84-130, the following parameters must be set.
1. The motor data
P201-P207
must be set according to the identification plate.
2. The motor stator resistance P208 is determined at 20°C with
P220 = 1
3. Function of Analog Input 2,
P400 [-04] = 30
(motor temperature)
4. Analog Input 2 mode,
P401 [-02] = 1
(negative temperatures are also measured)
(from firmware version: V1.2)
5. Matching of Analog Input 2:
P402 [-02] = 1.54V
and
P403 [-03] = 2.64V
(with R
V
= 2.7 kOhm)
6.
Matching of time constants:
P161 [-02] = 400ms
(Filter time constant is at a maximum)
Parameter (P161) is a module parameter. This cannot be set on the frequency inverter, but rather directly on the I/O-module.
Communication is carried out e.g. via the direct connection of a ParameterBox to the RS232 interface of the module or by the
connection of the frequency inverter via the system bus. (Parameter (P1101) object selection
→
… )
7. Motor temperature control (display):
P739 [-03]
NOTE
For the determination of the motor stator resistance, the temperature must be within the range
15 … 25°C.
Overtemperature of the motor is monitored simultaneously and at 155°C (switching threshold as
for thermistor) the drive is shut down with error message E002.
Содержание SK 200E Series
Страница 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 54: ...NORDAC SK 200E Manual 54 Subject to technical alterations BU 0200 GB 2 9 5 EC declaration of conformity...
Страница 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Страница 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Страница 263: ...10 Keyword index BU 0200 GB 263...
Страница 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Страница 265: ...The Nordac SK 200E is available to order from www inverterdrive com...