NORDAC SK 200E Manual
250
BU
0200
GB
Addressing
If several frequency inverters are connected to a system bus, these devices must be assigned with unique
addresses. For preference, this is carried out via the DIP switches on the underside of the SK200E (Section
5.1.2). For the use of CANopen absolute encoders, the encoders must be assigned to the relevant FI via the
node ID. If, for example, there are one encoder and four frequency inverters on the system bus and the
encoder is to operate with FI3, the node ID 37 must be set on the encoder, see the following table.
Addressing via DIP switches
Resulting Node ID
Frequency inverter
DIP 2
DIP 1
Frequency inverter
Node ID
Absolute value
encoder
FI1 OFF
OFF
32
33
FI2 OFF
ON
34
35
FI3 ON
OFF
36
37
FI4 ON
ON
38
39
For field bus modules, no assignment of addresses is necessary. The module identifies all the frequency
inverters automatically. Access to the individual inverters is via the field bus master (SPS). Details of how
this is carried out are explained in the relevant bus instructions.
I/O extensions must be assigned to the relevant frequency inverter. This is carried out by means of a DIP
switch on the I/O module. A special case for the I/O extensions is the "Broadcast" mode. In this mode, the
data of the I/O extension (analog values, inputs etc.) are sent to all inverters simultaneously. Via the
parameterisation in each individual frequency inverter, a decision is made as to which of the received values
are to be used. Further details of the settings can be obtained from this manual (See also Section 3.4.3 or
3.5.4).
NOTE
Care must be taken that each address is only assigned once. In a CAN-based network double
assignment of addresses may lead to misinterpretation of the data and therefore undefined
activities in the system.
Integration of devices from other manufacturers
In principle, the integration of other devices into this bus system is possible. These must support the
CANopen protocol and a 250kBaud baud rate. The address range (Node ID) 1 to 4 is reserved for additional
CANopen masters. All other participants must be assigned addresses between 50 and 79.
Содержание SK 200E Series
Страница 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 54: ...NORDAC SK 200E Manual 54 Subject to technical alterations BU 0200 GB 2 9 5 EC declaration of conformity...
Страница 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Страница 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Страница 263: ...10 Keyword index BU 0200 GB 263...
Страница 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Страница 265: ...The Nordac SK 200E is available to order from www inverterdrive com...