NORDAC SK 200E Manual
170
Subject to technical alterations BU
0200
GB
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P426
Quick stop time
S
P
0 ... 320.00 s
{ 0.10 }
Setting of the stop time for the quick stop function that can be triggered either via a digital input,
the bus control, the keyboard or automatically in case of a fault.
Quick stop time is the time for the linear frequency decrease from the set maximum frequency
(P105) to 0Hz. If an actual setpoint <100% is being used, the quick stop time is reduced
correspondingly.
P427
Quick stop on error
S
0 ... 2
{ 0 }
Activation of automatic emergency stop following error
0 = Disabled:
Automatic quick stop following error is deactivated
1 =
reserved
2 = Enabled:
Automatic quick stop following fault
P428 Automatic
starting
S
In the standard setting (P428 =
0
Æ
Off
) the inverter requires a flank for enable (signal change
from "Low
Æ
High") at the applicable digital input.
In the setting
On
Æ
1
the FI reacts to a High level. This function is only possible if the FI is
controlled using the digital inputs. (see P509=0/1)
In certain cases, the FI must start up directly when the mains are switched on. This means that
P428 =
1
Æ
On
can be set. If the enable signal is permanently switched on, or equipped with a
cable jumper, the FI starts up immediately.
NOTE:
The "Automatic start" function can only be used if a digital input of the frequency
inverter (DIN 1 … DIN 4) is parameterised to the function "Enable right" or "Enable
left" and this input is permanently set to "High". The digital inputs of the
Technology Unit modules (e.g.: SK CU4 - IOE) do not support this "automatic start"
function.
0 ... 1
{ 0 }
NOTE:
The "Automatic start" can only be activated if the frequency inverter has been
parameterised to local control ((P509) setting { 0 } or { 1} ).
Содержание SK 200E Series
Страница 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 54: ...NORDAC SK 200E Manual 54 Subject to technical alterations BU 0200 GB 2 9 5 EC declaration of conformity...
Страница 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Страница 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Страница 263: ...10 Keyword index BU 0200 GB 263...
Страница 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Страница 265: ...The Nordac SK 200E is available to order from www inverterdrive com...