9.2.2
Process controller parameter settings
(Example: Setpoint frequency: 50 Hz, control limits: +/- 25%)
P105 (Maximum frequency) [Hz]
:
[ ]
[ ]
[ ]
⎟
⎠
⎞
⎜
⎝
⎛
×
+
≥
%
%
.
.
100
415
P
Hz
q
Setpointfr
Hz
q
Setpointfr
Example:
=
×
+
≥
%
100
%
25
50
50
Hz
Hz
62,5Hz
P400 [-01] (Funct. Analog input1)
:
"2“"
(frequency addition)
P411 (Setpoint frequency) [Hz]
: Setpoint frequency with 10V at analog input 1
Example:
50 Hz
P412 (Process controller setpoint) : Central setting of compensating roller / factory setting
5V
(adjust if
necessary)
P413 (P-controller) [%]
: factory setting
10%
(adjust if necessary)
P414 (I-controller) [%/ms]
: recommended
100
%/s
P415 (Limit +/-) [%]
: Control limit (see above)
Note:
Parameter P415 is used as a control limit after the PI controller.
Example:
25%
of setpoint
P416 (Ramp time PI setpoint) [s]
: factory setting
2s
(if necessary match to controller characteristics)
P420 [-01] (Funct. Digital input 1)
:
"1"
Enable right
P400 [-02] (Funct. Analog input 2) :
"6"
PI process controller actual value
Содержание SK 200E Series
Страница 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 54: ...NORDAC SK 200E Manual 54 Subject to technical alterations BU 0200 GB 2 9 5 EC declaration of conformity...
Страница 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Страница 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Страница 263: ...10 Keyword index BU 0200 GB 263...
Страница 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Страница 265: ...The Nordac SK 200E is available to order from www inverterdrive com...