NORDAC SK 200E Manual
150
Subject to technical alterations BU
0200
GB
6.1.3
Motor data / characteristic curve parameters
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P200 Motor
list
P
The factory settings for the motor data can be edited with this parameter. The factory setting in
parameters P201...P209 is a 4-pole DS standard motor with the nominal FI power setting.
By selecting one of the possible digits and pressing the OK key, all motor parameters
(P201…P209) are adjusted to the selected standard power. The basis for the motor data is a 4-
pole DS standard motor
0 = No change
of data
1 = No motor:
In this setting, the FI operates without current control, slip compensation and
pre-magnetising time, and is therefore not recommended for motor applications.
Possible applications are induction furnaces or other applications with coils and
transformers. The following motor data is set here:
50.0Hz / 1500rpm / 15.0A / 400V / 0.00kW / cos
ϕ
=0.90 / star / R
S
0.01
Ω
/ I
EMPTY
6.5A
2 =
0.25 kW 230V
3 =
0.33 HP 230V
4 =
0.25 kW 400V
5 =
0.33 HP 460V
6 =
0.37 kW 230V
7 =
0.50 HP 230V
8 =
0.37 kW 400V
9 =
0.50 HP 460V
10 =
0.55 kW 230V
11 =
0.75 HP 230V
12 =
0.55 kW 400V
13 =
0.75 HP 460V
14 =
0.75 kW 230V
15 =
1.0 HP 230V
16 =
0.75 kW 400V
17 =
1.0 HP 460V
18 =
1.1 kW 230V
19 =
1.5 HP 230V
20 =
1.1 kW 400V
21 =
1.5 HP 460V
22 =
1.5 kW 230V
23 =
2.0 HP 230V
24 =
1.5 kW 400V
25 =
2.0 HP 460V
26 =
2.2 kW 230V
27 =
3.0 HP 230V
28 =
2.2 kW 400V
29 =
3.0 HP 460V
30 =
3.0 kW 230V
31 =
3.0 kW 400V
32 =
4.0 kW 230V
33 =
5.0 HP 230V
34 =
4.0 kW 400V
35 =
5.0 HP 460V
36 =
5.5 kW 230V
37 =
7.5 HP 230V
38 =
5.5 kW 400V
39 =
7.5 HP 460V
40 =
7.5 kW 230V
41 =
10 HP 230V
42 =
7.5 kW 400V
43 =
10 HP 460V
44 =
11.0 kW 400V
45 =
15.0 HP 460V
46 =
15.0 kW 400V
47 =
20.0 HP 460V
48 =
18.5 kW 400V
49 =
25.0 HP 460V
50 =
22.0 kW 400V
51 =
30.0 HP 460V
52 =
30.0 kW 400V
53 =
40.0 HP 460V
0 ... 45
{ 0 }
NOTE:
As P200 returns to = 0 after the input confirmation, the control of the set motor can
be implemented via parameter P205.
If DIP switch 7 (50/60Hz operation, Section 5.1.1) is switched over, the appropriate
nominal motor data according to the FI power rating are reloaded from the P200
list.
P201
Nominal frequency
S
P
10.0 ... 400.0 Hz
{
∗
}
The motor nominal frequency determines the V/f break point at which the FI supplies the
nominal voltage (P204) at the output.
P202 Nominal
speed
S
P
150 ... 24000 rpm
{
***
}
The nominal motor speed is important for the correct calculation and control of the motor slip
and the speed display (P001 = 1).
P203 Nominal
current
S
P
0.1 ... 300.0 A
{
***
}
The nominal motor current is a decisive parameter for the current vector control.
***
These settings are dependent on the nominal power of the FI or the selection in parameter P200.
Содержание SK 200E Series
Страница 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 54: ...NORDAC SK 200E Manual 54 Subject to technical alterations BU 0200 GB 2 9 5 EC declaration of conformity...
Страница 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Страница 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Страница 263: ...10 Keyword index BU 0200 GB 263...
Страница 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Страница 265: ...The Nordac SK 200E is available to order from www inverterdrive com...