NORDAC SK 200E Manual
142
Subject to technical alterations BU
0200
GB
6.1.1
Operating displays
The abbreviations used are described in Section 9.12 “Abbreviations in this Manual".
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P000
Operating para
meter
disp
lay
0.01 ... 9999
In the SimpleBox (SK CSX-3H) display, the parameter value
online
selected in P100 is
displayed.
P001
Selection of disp
lay
value
0 ... 63
{ 0 }
0 = Actual frequency [Hz]
, is the actual output frequency supplied by the FI.
1 =
Rotation
speed [1/min]
, is the actual rotation speed as calculated by the FI.
2 = Setpoint frequency [Hz]
: the output frequency equivalent to the actual setpoint. This
need not match the actual output frequency.
3 = Current [A]
: the actual output current measured by the FI.
4 = Torque current [A]
: the torque-developing output current of the FI.
5 = Voltage [V~ ]
: the actual alternating voltage being output by the FI.
6 = D.c. link
circuit
voltage [V =]
: the internal DC voltage of the FI. Amongst other things,
this depends on the level of the mains voltage.
7 = cos Phi,
the currently calculated value of the power factor.
8 = Apparent power [kVA]
: the actual apparent power calculated by the FI.
9 = Real power [kW]
: the actual effective power calculated by the FI.
10 = Torque [%]
: the actual torque calculated by the FI.
11 = Field [%]:
the actual field in the motor calculated by the FI.
12 = On-time
(operating hours)
[h]:
time that voltage is applied to the FI.
13 = Run-time
(enabled operating hours)
[h]:
time for which the FI has been enabled.
14 = Analog input 1 [%],
actual value AIN1 of the first I/O extension SK xU4-IOE.
15 = Analog input 2 [%],
actual value AIN2 of the second I/O extension SK xU4-IOE.
16 = Position setpoint
value
Æ
Posicon, BU 0210
17 = Position current val
ue
Æ
Posicon, BU 0210
19 = Temp
erature
of heat sink [°C]
: current temperature of the FI heat sink.
20 = Usage rate motor [%]
: average motor load, based on the known motor data
(P201...P209).
21 = Usage rate braking res
istor
- R [%]
: average braking resistor load, based on the known
resistance data (P556...P557).
22 = Internal temperature [°C]
, current temperature in FI housing.
23 = Motor temperature [°C]
, only in combination with the analog input and appropriate
wiring (KTY84).
30 = Current
setpoint
value of the
m
otor
p
otentiometer
-S
etpoint value
[Hz]
, display of
the setpoint which can be set in advance (without the drive unit running) via the motor
potentiometer function 71 / 72 (See parameter P420).
50 =
Act
ual
inc
remental encoder
pos
ition
value
Æ
Posicon, BU 0210
51 =
Act
ual
abs
olute encoder
pos
ition
value
Æ
Posicon, BU 0210
52 =
Act
ual
pos
ition
difference
Æ
Posicon, BU 0210
53 =
Act
ual
pos
ition
diff
erence
A
bsolute
/I
ncremental
Æ
Posicon, BU 0210
54 =
Act
ual
pos
ition
diff
erence
C
alculated
/M
easured
Æ
Posicon, BU 0210
60 = R Stator Ident
: stator resistance, automatic determination of motor data, P220
61 = R Rotor Ident
: rotor resistance, automatic determination of motor data, P220
62 = L Scat
ter
Stator Ident
, stator leakage inductance, from automatic determination of
motor data, P220
63 = L Stator Ident
: stator inductance, from automatic determination of motor data, P220
Содержание SK 200E Series
Страница 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 54: ...NORDAC SK 200E Manual 54 Subject to technical alterations BU 0200 GB 2 9 5 EC declaration of conformity...
Страница 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Страница 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Страница 263: ...10 Keyword index BU 0200 GB 263...
Страница 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Страница 265: ...The Nordac SK 200E is available to order from www inverterdrive com...