6 Parameterisation
BU 0200 GB
Subject to technical alterations
191
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P709
[-01]
...
[-09]
Analog input
voltage
-100.0 ... 100.0 %
Displays the measured analog input value.
[-01] =
Potentiometer 1
, internal FI potentiometer P1 (Section 5.1.3), for the adjustment
of “maximum frequency”, “minimum frequency” and “ramp time”
[-02] =
Potentiometer 2
, internal FI potentiometer P2 (Section 5.1.3) with fixed steps, the
function can also be entered via the DIP switch.
[-03] =
External analog input 1
, AIN1 of the first I/O extension (SK xU4-IOE).
[-04] =
External analog input 2
, AIN2 of the first I/O extension (SK xU4-IOE).
[-05] =
Setpoint module
, in preparation
[-06] =
Analog function
digital input
2
, analog function of the FI digital input 2
[-07] =
Analog function
digital input
3
, analog function of the FI digital input 3
[-08] =
External
analog
input
1 2nd IOE
, AIN1 of the second I/O extension
(SK xU4-IOE) (= analog input 3).
[-09] =
External
analog
input
2 2nd IOE
, AIN2 of the second I/O extension
(SK xU4-IOE) (= analog input 4).
P710
[-01]
[-02]
Analog output volta
ge
0.0 ... 10.0 V
Displays the delivered value of analog output.
[-01] =
First IOE,
AOUT of the first I/O extension (SK xU4-IOE)
[-02] =
Second IOE,
AOUT of the second I/O extension (SK xU4-IOE)
P711 Digital
output status
Shows the actual status of the digital outputs of the frequency inverter.
00 ... 11
(bin)
or
0 ... 3
(hex)
Bit 0 =
Digital output 1
Bit 1 =
Mechanical brake
P714 Operating
time
0.00 ... ___ h
This parameter shows the time for which the FI was connected to the mains and was ready for
operation.
P715 Running
time
0.00 ... ___ h
This parameter shows the time for which the FI was enabled and supplied current to the output.
P716 Current
frequency
-400.0 ... 400.0 Hz
Displays the actual output frequency.
P717 Current
rotation
speed
-9999 ... 9999 rpm
Displays the actual motor speed calculated by the FI.
P718
[-01]
...
[-03]
Current set
point
freq
uency
-400.0 ... 400.0 Hz
Displays the frequency specified by the setpoint.
[-01] =
Actual setpoint frequency from the setpoint source
[-02] =
Actual setpoint frequency after processing in the FI status machine
[-03] =
Actual setpoint frequency after the frequency ramp
Содержание SK 200E Series
Страница 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 54: ...NORDAC SK 200E Manual 54 Subject to technical alterations BU 0200 GB 2 9 5 EC declaration of conformity...
Страница 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Страница 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Страница 263: ...10 Keyword index BU 0200 GB 263...
Страница 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Страница 265: ...The Nordac SK 200E is available to order from www inverterdrive com...