9.2 Process controller
The process controller is a PI controller, with which it is possible to limit the controller output. In addition, the
output is standardised to a percentage of a master setpoint value. This provides the possibility of controlling
an upstream drive unit with the master setpoint value and adjusting it with the PI controller.
+
-
X
x1
x2
y
x1*x2
y=
100 %
+
+
Fig.: Process controller flow-chart
9.2.1
Process controller application example
M
M
M
M
0V
10V
Frequency inverter
Setpoint of pilot machine
AIN 1
Enabled right
DIN 1
Actual position CR
AIN 2
Nominal position CR
via parameter P412
Master set-
point value
Analog input 1
(P400[-03]=2)
or
Analog Input 2
Setpoint
P412 = 0.0-10.0V
Actual
value
Analog input 1
(P400[-03]=6)
or
Analog Input 2
Ramp time PI setpoint P416
P-Factor P413
I-Factor P414
PI controller
Min. limit
P466
Lead value
Analog input
(P400[..] = 16)
Start-up time P102
Setpoint ramp
max. limit
P415
Controlled drive via CR
Compensating roller = CR (dancer roller)
Pilot machine
Actual
position
of CR via
potentiometer
0-10V
Centre 5V
nominal
position
f
t
Setpoint of
pilot machine
Controller
limit P415 in
% of setpoint
Controller
limit P415
Содержание SK 200E Series
Страница 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 54: ...NORDAC SK 200E Manual 54 Subject to technical alterations BU 0200 GB 2 9 5 EC declaration of conformity...
Страница 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Страница 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Страница 263: ...10 Keyword index BU 0200 GB 263...
Страница 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Страница 265: ...The Nordac SK 200E is available to order from www inverterdrive com...