SK CU4-IOE-, I/O extension
The internal I/O units can record sensor and actuator signals. These can be used for a drive function or
forwarded to a host bus system (e.g. Profibus or CANopen).
•
2x digital inputs
•
2x analog inputs
•
1x analog output
•
Status LEDs: Module status, module error,
Dig In 1, Dig. In 2
•
DIP switches for selection
0 - 10V, -10 - 10V, 0 - 20mA, 4 - 20mA
•
DIP switches for: addressing, bus termination
The terminal block of the Customer Unit SK CU4-IOE… is divided into two potential levels.
NOTE
Looping of the 24V supply voltage
(terminals 44/40)
is in principle possible, however, a
maximum current load of
2A
for the
SK CU4-IOE
must not be exceeded!
12
15
16
11
17
12
13
14
11
40
78
77
C2
C1
40
44
AIN1+
AOUT
24V
GND
Sys+
Sys-
GND A
10V Ref.
Analog input 1
Connection of the 24V supply volt-
age from the SK 200E
System bus connection
from the SK 200E
Potential level:
System bus
Potential level:
analog part
Connection to the
terminal block of the SK CU4-IOE
AIN1-
Analog output
Analog input 2
AIN2+
GND A
10V Ref.
AIN2-
Similar to illustration
Содержание SK 200E Series
Страница 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 54: ...NORDAC SK 200E Manual 54 Subject to technical alterations BU 0200 GB 2 9 5 EC declaration of conformity...
Страница 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Страница 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Страница 263: ...10 Keyword index BU 0200 GB 263...
Страница 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Страница 265: ...The Nordac SK 200E is available to order from www inverterdrive com...