NORDAC SK 200E Manual
68
Subject to technical alterations BU
0200
GB
3.4.2
Potentiometer Adapter, SK CU4-POT
The digital signals R and L can be directly applied to the corresponding digital inputs 1 and 2 of the SK 200E.
The potentiometer (0-10) can be evaluated via a 24V module or I/O extension and converted to proportional
impulses (frequency). These impulses can then be evaluated via the digital input 2 or 3
(P420 [02]/[03] = 26/27) of the SK 200E in the form of a setpoint value (P400 [-06]/[-07]).
Module
Connection: Terminal
No.
Pin
Colour
SK CU4-POT
FI
Mains unit
Function
1
Brown
24V supply voltage
44
2
Black
Enable R (e.g. DIN 1)
21
3
White
Enable L (e.g. DIN2)
22
Rotary switch L - OFF - R
4
White
Access to AIN1+
14
5
Brown
10V reference voltage
11
6
Blue
Analog Ground AGND
12
Potentiometer 10k
Ω