2.9.2.2
Customer Units for ATEX Zone 22 3D
Name
Part Number
Approved for
ATEX Zone 22 3D
Not approved for
ATEX Zone 22 3D
SK CU4-PBR
275271000
x
SK CU4-CAO
275271001
x
SK CU4-DEV
275271002
x
SK CU4-IOE
275271006
x
SK CU4-POT
275271207
x
SK CU4-24V-123-B
275271108
x
SK CU4-24V-140-B
275271109
x
SK ATX-POT
275142000
x
The SK 2x5E for Category 3D can be equipped with an ATEX-compliant potentiometer, which can be used
to adjust a setpoint (e.g. speed) on the device. The potentiometer is used with an M20-M25 extension in one
of the M25 cable glands. The selected setpoint can be adjusted with a screwdriver. Due to the removable
screw closing cap, this component complies with
ATEX requirements. Permanent operation may only
be carried out with the cap closed.
Frequency setpoint setting
with a screwdriver
Resistance of the potentiometer 10 kOhm
Wire colours on the
potentiometer
Name
Terminal CU4-24V
Terminal CU4-IOE
Red +10V
reference
[11]
[11]
Black
AGND / 0V
[12]
[12]
Green
Analog input
[14]
[14] / [16]
NOTE:
For the use of a potentiometer with frequency inverter SK 2x5E a Customer Unit CU4-24V-xxx-B
or CU4-IOE is necessary.
Содержание SK 200E Series
Страница 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 54: ...NORDAC SK 200E Manual 54 Subject to technical alterations BU 0200 GB 2 9 5 EC declaration of conformity...
Страница 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Страница 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Страница 263: ...10 Keyword index BU 0200 GB 263...
Страница 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Страница 265: ...The Nordac SK 200E is available to order from www inverterdrive com...