2 Assembly and installation
BU 0200 GB
Subject to technical alterations
29
2.3 Brake resistor (BR)
During dynamic braking (frequency reduction) of a three phase motor, electrical energy is returned to the
frequency inverter. In order to avoid switch-off of the FI due to excess voltage and internal or external
braking resistor can be used. With this, the integrated brake chopper (electronic switch) pulses the link
circuit voltage (switching threshold approx. 420V/720V DC, according to the mains voltage) into the braking
resistor. Here the excess energy is converted into heat.
CAUTION
The braking resistance and all other metal components can heat up to temperatures above
70°C.
When mounting, sufficient distance from neighbouring components must be maintained.
When working on the components, allow sufficient cooling time beforehand
2.3.1
Internal brake resistor SK BRI4-…
The internal brake resistor can be used if only slight, short braking phases are to be expected.
NOTE
With the use of internal resistors, the DIP switch 8 must be set to “On”. This is important in
order to activate a limitation of the peak power of the brake resistor. Otherwise, the brake
resistor may be damaged during operation.
Alternatively, a suitable power limit can also be set in P555, P556 and P557. However, this
is only effective if DIP 8 is set to the “Off” position.
Содержание SK 200E Series
Страница 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 54: ...NORDAC SK 200E Manual 54 Subject to technical alterations BU 0200 GB 2 9 5 EC declaration of conformity...
Страница 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Страница 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Страница 263: ...10 Keyword index BU 0200 GB 263...
Страница 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Страница 265: ...The Nordac SK 200E is available to order from www inverterdrive com...