6 Parameterisation
BU 0200 GB
Subject to technical alterations
187
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P558 Flux
delay
(Excitation time)
S
P
0 / 1 / 2 ... 500 ms
{ 1 }
The ISD control can only function correctly if there is a magnetic field in the motor. For this
reason, a DC current is applied before starting the motor. The duration depends on the size of
the motor and is automatically set in the factory setting of the FI.
For time critical applications, the excitation time can be set or deactivated.
0 =
switched off
1 =
automatic
calculation
2 ... 500 =
according to set time in [ms]
NOTE:
Setting values that are too low can reduce the dynamics and starting torque.
P559
DC run-on time
S
P
0.00 ... 30.00 s
{ 0.50 }
Following a stop signal and the braking ramp, a direct current is briefly applied to the motor to
fully bring the drive to a stop. Depending on the inertia, the time for which the current is applied
can be set in this parameter.
The current level depends on the previous braking procedure (current vector control) or the
static boost (linear characteristic).
P560
Mode of param
eter
save
S
0 ... 2
{ 1 }
0 = Only in RAM,
changes to the parameter settings are no longer saved on the EEPROM.
All previously saved settings are retained, even if the FI is disconnected from the
mains.
1 = RAM and EEPROM,
all parameter changes are automatically written to the EEPROM
and remain stored there even if the FI is disconnected from the mains supply.
2 = Off,
no storage in the RAM and EEPROM possible ( No parameter changes are
accepted)
NOTE:
If BUS communication is used to implement parameter changes, it must be
ensured that the maximum number of write cycles (100,000 x) in the EEPROM is
not exceeded.
Содержание SK 200E Series
Страница 1: ...GB BU 0200 NORDAC SK 200E Frequency inverter manual Quick commissioning page 123...
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 54: ...NORDAC SK 200E Manual 54 Subject to technical alterations BU 0200 GB 2 9 5 EC declaration of conformity...
Страница 138: ...NORDAC SK 200E Manual 138 Subject to technical alterations BU 0200 GB 5 4 6 Certificate...
Страница 262: ...NORDAC SK 200E Manual 262 BU 0200 GB...
Страница 263: ...10 Keyword index BU 0200 GB 263...
Страница 264: ...NORDAC SK 200E Manual 264 BU 0200 GB Part No 607 2002 1310...
Страница 265: ...The Nordac SK 200E is available to order from www inverterdrive com...