must specify an appropriate consumer (slot option) of the event.
Specifies the Modbus register addressing mode.
The standard addressing mode allows menus up to 162 and parameters up to 99 to be accessed,
for any parameter above 99, the modified addressing mode bust be used, however, this mode limits
the highest accessible menu number to 63.
This parameter specifies an IP address for priority connection 1.
This feature is not yet implemented.
S.15.013
Modbus Register Addressing Mode
Minimum
0
(Display: Standard)
Maximum
1
(Display: Modified)
Default
0
(Display: Standard)
Units
None
Type
8 Bit User Save
Update Rate
Module reset, Modbus
interface reset or Modbus
interface enable
Display Format
None
Decimal Places
0
Coding
RW, Txt, BU
Value
Text
Description
0
Standard
(mm x 100) + ppp - mm<=162 and ppp<=99
1
Modified
(mm x 256) + ppp - mm<=63 and ppp<=255
S.15.020
Priority Connection 1
Minimum
0
(Display: 0.0.0.0)
Maximum
4294967295
(Display: 255.255.255.255)
Default
0
(Display: 0.0.0.0)
Units
None
Type
32 Bit User Save
Update Rate
Module reset, Modbus
interface reset or Modbus
interface enable
Display Format
IP Address
Decimal Places
0
Coding
RW, BU
NOTE