138
SI-Ethernet User Guide
Issue: 3
Table 7-5 Start register addressing
7.2.7
FC03 – Read multiple registers
This function code allows a contiguous array of registers to be read. The maximum number of
registers that can be read is 120, this allows up to 120 16-bit parameters or 60 32-bit parameters
to be read in a single transaction. If this is exceeded the server will issue an exception response
code 2.
Master request data
Slave response data
The normal response includes the function code, number of data bytes in the read block followed
by the register data (unless an exception occurs).
If 32-bit parameter addressing is used, then for each parameter read:
•
Two 16-bit registers must be used in the request
•
The register data in the response will contain 4 bytes of data
Example
To read drive parameters
0.20.021
to
0.20.023
(transaction ID = 42) with 32-bit data access and
standard addressing:
CT Parameter
Addressing mode
Protocol register
s.mm.ppp
Standard
mm * 100 + ppp - 1
Modified
mm * 256 + ppp - 1
Examples
16-bit
32-bit
Decimal
Hex (0x)
Decimal
Hex (0x)
0.01.021
Standard
120
00 78
16504
40 78
Modified
276
01 14
16660
41 14
0.01.000
Standard
99
00 63
16483
40 63
Modified
255
00 FF
16639
40 FF
3.70.001
Standard
7000
1B 58
23384
5B 58
Modified
N/A
N/A
N/A
N/A
0.03.161
Standard
N/A
N/A
N/A
N/A
Modified
928
03 A0
17312
43 A0
Byte
Description
Byte
Description
7
Function code 0x03
7
Function code 0x03
8
Start register address
(MSB)
8
Length of data in read block
(Bytes)
9
Start register address
(LSB)
9
Register data
(MSB)
10
Number of 16-bit registers
(MSB)
10
Register data
(LSB)
11
Number of 16-bit registers
(LSB)