SI-Ethernet User Guide
41
Issue: 3
Sa
fe
In
Me
ch
E
G
Par
amet
er
Key
an
PC T
Sec
Di
G
Ind
ex
When DHCP is enabled, the following parameters will become read-only immediately (no reset
required):
•
IP Address (
S.02.006
)
•
Subnet Mask (
S.02.007
)
•
Default Gateway (
S.02.008
)
•
Primary DNS (
S.02.009
)
•
Secondary DNS (
S.02.010
)
Controls and displays the IP address of the module.
If DHCP is enabled this parameter becomes read-only, and until an IP address is allocated to the
module will display 0.0.0.0. If no DHCP server replies to the DHCP request within approximately 1
minute, then the Ethernet interface will automatically assign a link-local IP address in the range
169.254.0.0 to 169.254.255.255
If DHCP is disabled the module will initialize, on reset or power cycle, with the IP address stored for
the parameter.
Controls and displays the subnet mask of the module.
If DHCP is enabled this parameter becomes read-only, and until a subnet mask is allocated to the
module will display 0.0.0.0.
If DHCP is disabled the module will initialize, on reset or power cycle, with the subnet mask stored
for the parameter.
S.02.006
IP Address
Minimum
0
(Display: 0.0.0.0)
Maximum
4294967295
(Display:255.255.255.255)
Default
3232235876
(Display:192.168.1.100)
Units
None
Type
32 Bit User Save
Update Rate
DHCP enabled: write on
event;
DHCP disabled: read on reset
Display Format
IP Address
Decimal Places
0
Coding
RW, BU
S.02.007
Subnet Mask
Minimum
0
(Display: 0.0.0.0)
Maximum
4294967295
(Display:255.255.255.255)
Default
4294967040
(Display:255.255.255.0)
Units
None
Type
32 Bit User Save
Update Rate
DHCP enabled:
write on event;
DHCP disabled:
read on reset
Display Format
IP Address
Decimal Places
0
Coding
RW, BU
Содержание Unidrive M600
Страница 1: ...User Guide SI Ethernet and Unidrive M Onboard Ethernet Part Number 0478 0137 03 Issue 3 ...
Страница 16: ...16 SI Ethernet User Guide Issue 3 Figure 4 3 Typical network topologies ...
Страница 215: ......