33
diallEr - PrOgrammiNg
D. Prog
neSS D24 Control Panel - inStallation & PrograMMing Manual
OPTION No DESCRIPTION
DEFAULT
P68E
Zone reporting Abort Delay
30 seconds
ZONE rEPOrTiNg abOrT dElay
any zone can be programmed for abort operation which means the zone must
remain unsealed for the specified time before it is recognised as an alarm.
P68e Abort DeLAY tIme.
there are two time ranges.
enter a value of 0–100 for 0–100 seconds.
enter a value of 101–220 for 1 to 120 minutes.
P69e Abort DeLAY ZoNeS
Selects the zones which will have abort Delay time.
Press P69e zone number e zone number e... etc up to 24 zones.
P68e, P69e
prOgraM MOde leVel:
Installer, Remote by PC
FaCtOrY deFault:
P68E: 30 seconds
P69E: no zones
tO prOgraM:
p68e
[time]
e
(Enter 0–100 seconds or 101–220 for 1–120
minutes)
p69e
[zone]
e
[zone]
e
... etc
OPTION No
DESCRIPTION
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Zones
P69E
Abort Delay Zones
OPTION No DESCRIPTION
DEFAULT
P70E
P71E
Time before first test call
Test call interval
168 hours
0 (disabled)
TEST CallS
the D24 can be programmed to send periodic test calls to the Central Station.
P70e tIme before fIrSt teSt CALL.
this option is used to set the preferred time for test Calls. Programmable from
0–255 hours. enter a value between 0 and 255.
examples:
A/ New Installation:
Set the time before the first test call.
e.g., if you are programming the panel at 5pm and you want test calls to be sent
at 1am. enter P70e 8e (5pm + 8hrs =1am).
b/ existing Installation:
to reset the time that test calls are sent.
e.g., our example panel is sending test calls at 1am and you want to change it
to 2am. if you are programming the panel at 3pm, enter P70e 11e (3pm + 11hrs
=2am).
P71e teSt CALL INterVAL.
Sets the time between test calls. Commonly set for 168 hours, (7 days), (ask your
central station).
Programmable from 0–255 hours. enter a value between 0 and 255.
a value of 0 (zero) disables test calls (factory default).
P70e, P71e
prOgraM MOde leVel:
Installer, Remote by PC
FaCtOrY deFault:
Time before first test call: 168 hours
Test call interval: 0 (disabled)
tO prOgraM:
p70e
[time]
e
(0–255 hours)
p71e
[time]
e
(0–255 hours)
HOURS
DAYS
24
1
48
2
72
3
96
4
120
5
144
6
168
7
192
8
216
9
240
10
test Call times commence on exit from installer program mode.