ENTry dElay TimErS
the entry Delay time is the time given to Disarm the panel after an entry Delay
zone is unsecured.
p17e
this is the global entry Delay time. any value programmed at this option also
changes all other entry Delay timers.
p170e
this is the entry Delay timer for zones assigned to more than one area. any value
programmed at this option also changes P17e.
(P171E, P172E, P173E are not
affected).
p171e, p172e, p173e
area 1, 2 and 3 entry Delay times can be individually programmed with different
values.
P17e – P173e
prOgraM MOde leVel:
User, Installer, Remote by PC
FaCtOrY deFault:
see table
tO prOgraM:
p
[Option No]
e
[New time]
e
eXaMple:
To program 30 sec Global Entry Delay: P17E 30E
nOtes:
• All timers are programmable from 1–99
seconds
EXiT dElay TimE
the exit Delay time is the time given to vacate the premises after the panel is
armed. all zones except 24 hour zones are disabled during the exit Delay time.
p18e
this is the global exit Delay time. any value programmed at this option also
changes all other exit Delay timers. if different exit delays are required for each
area use P181e–P183e.
p181e, p182e, p183e
area 1, 2 and 3 exit Delay times can be individually programmed with different
values.
P18e – P183e
prOgraM MOde leVel:
User, Installer, Remote by PC
FaCtOrY deFault:
see table
tO prOgraM:
p
[Option No]
e
[New time]
e
eXaMple:
To program 55 sec Global Exit Delay:
p18e 55e
nOtes:
• All timers are programmable from 1–99
seconds
OPTION No
DESCRIPTION
DEFAULT
P17E
P170E
P171E
P172E
P173E
P18E
P181E
P182E
P183E
Entry Delay Time
Entry Delay Time for zones in multiple areas
Entry Delay Time for AREA 1
Entry Delay Time for AREA 2
Entry Delay Time for AREA 3
Exit Delay Time
Exit Delay Time for AREA 1
Exit Delay Time for AREA 2
Exit Delay Time for AREA 3
20 Seconds
Seconds
Seconds
Seconds
Seconds
Seconds
Seconds
Seconds
20
20
20
20
60
60
60
60
Seconds
P28E
Siren Reset Time
10 Minutes
SirEN rESET TimE
the Siren reset time sets the duration of the Siren and reset outputs.
Programmable from 1 – 99 minutes
P28e
prOgraM MOde leVel:
Installer, Remote by PC
FaCtOrY deFault:
10 Minutes
tO prOgraM:
p
[Option No]
e
[New time]
e
eXaMple:
To program 5 minute Siren Time:
p28e 5e
prOgraMMIng FeedBaCK
When programming timers, the existing
time and then the new time is ‘read back’ by
flashing the numeric keypad icons 0–9.
1.
Press:
p [Option no] e
the existing time
is displayed by the keypad.
2.
Enter the new time:
[new time] e
, the
new time will be displayed.
NOTe: The new time can be entered
immediately without waiting for the display
to finish the ‘read back’.
Содержание D24
Страница 1: ...Installation Programming MANUAL D 24 Control Panel and Dialler REV 1 9 ...
Страница 53: ...53 Ness D24 Control panel Installation Programming Manual Notes ...
Страница 59: ...59 Ness D24 Control panel Installation Programming Manual Notes ...
Страница 60: ...This page is intentionally blank ...