neSS D24 Control Panel - inStallation & PrograMMing Manual
0 hours
OPTION No
DESCRIPTION
1
2
3
4
5
6
7
8
Zones
P85E
P86E
Supervised Radio Zones
Radio Supervision time
SuPErviSEd radiO ZONES
this option assigns zones that will operate as radio Supervised types. this
applies to zones 1-8 only.
Supervised signals failure reports a Contact iD code 381 for that zone. the report
is sent once only.
the keypad will indicate radio Supervision by flashing the System icon and
continuous beeping.
P85e
prOgraM MOde leVel:
Installer, Remote by PC
FaCtOrY deFault:
no zones
tO prOgraM:
p85e
[zone]
e
[zone]
e
... etc
Toggles the option ON and OFF.
nOte:
Older Radio PIRs without a supervision option
should not be used on supervision-enabled
zones.
radiO SuPErviSiON TimE
the SuPerViSion tiMe is the time allowed between radio transmissions received
by the panel from any Supervised ness radio Pir (100–663, 100-691).
the SuPerViSion tiMe setting is from 01 to 24 hours.
P86e
prOgraM MOde leVel:
Installer, Remote by PC
FaCtOrY deFault:
0 hours (disabled)
tO prOgraM:
p86e
[0-24 hours]
e