4. STARTUP
4 - 7
(1) Slide switches (SW1-1 and SW1-2)
The combination of SW1-1 and SW1-2 enables you to switch communication method and set the test
operation mode (enabled/disabled). The following table lists the combinations of the switches.
In the test operation mode, the functions such as JOG operation, positioning operation, and machine
analyzer are available with MR Configurator2.
Slide switches (SW1)
Communication
Test operation mode
1
ON
2
CC-Link IE Field Network Disabled
1
ON
2
CC-Link IE Field Network Basic
Disabled
1
ON
2
Not available
Enabled
1
ON
2
For manufacturer setting
(2) Rotary switches (SW2/SW3)
Set the identification number of the servo amplifier in hexadecimal. From "00h (0)" to "FFh (255)" can be
set. The set value is used as the 4th octet of the IP address when the identification number is set
between "01h (1)" and "FFh (255)".