24 - 20
24. INVERTER CONNECTION
24.5 FREQROL Series Inverter Side Settings
24.5.8 Connecting FREQROL-F700/
F700P series
Communication settings
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating
each parameter.
(1) Communication port and corresponding parameters
(2) Communication settings of inverter
Set the following parameters using the PU (parameter
unit). Set Pr.160 (User group read selection) to 0 [The
simple mode and extended parameters can be
displayed] before making the parameter settings.
Do not change these parameters, even though they
can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
*1
Setting items are parameter names described in the manual
of FREQROL-F700 series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change
the parameters on the inverter to correspond with the GOT
settings.
*3
Inverter default values (No need to change)
*4
Since the value has been set as a default, no setting is
required when connecting to the PU connector on the
inverter side.
HINT
HINT
HINT
Automatic setting with Pr.999 (FREQROL-F700P
series only)
If Pr.999 is set as the following, the communication
settings other than [PU communication station
number] and [Communication EEPROM write
selection] can be automatically set in a batch to the
default communication settings of the GOT side.
*1
When monitoring the value of Pr.999, 9999 is always
monitored.
GOT connection
destination
Parameters corresponding to inverter
PU connector
Pr.79, Pr.117 to Pr.124, Pr.340, Pr.342
RS-485 terminal
Pr.79, Pr.331 to Pr.337, Pr.340 to Pr.342, Pr.549
Setting item
*1
Parameter No.
Set value
Contents of
setting
PU
connector
RS-
485
PU communication
station number
/RS-485
communication station
number
Pr.117
Pr.331
0 to 31
24.5.13 Station
number setting
PU communication
speed
/RS-485
communication speed
*2
Pr.118
Pr.332
192
*4
19200bps
PU communication
stop bit length
/
RS-485
communication stop bit
length
*2
Pr.119
Pr.333
10
Data length: 7bit
Stop bit length:
1bit
PU
communication parity
check
/
RS-485
communication parity
check
*2
Pr.120
Pr.334
1
Odd
Number of
PU communication
retries
/
RS-485 communication
retry count
Pr.121
Pr.335
9999
The inverter will
not come to an
alarm stop.
PU communication
check time interval
/
RS-485 communication
check time interval
Pr.122
Pr.336
9999
*4
Communication
check suspension
PU communication
waiting time setting
/
RS-485 communication
waiting time setting
Pr.123
Pr.337
0
0ms
PU communication
CR/LF selection
/
RS-485 communication
CR/LF selection
Pr.124
Pr.341
1
*3
With CR
Without LF
Protocol selection
-
Pr.549
0
*3
Mitsubishi inverter
protocol
Operation mode
selection
Pr.79
PU
connector
1
PU operation
mode
RS-485
0
*3
External operation
mode at power on
Communication startup
mode selection
Pr.340
PU
connector
0
*3
Refer to
Pr.79 settings.
RS-485
1
Network operation
mode.
Communication
EEPROM
write selection
Pr.342
0
*3
Written to RAM
and EEPROM
Parameter
No.
Set
value
Contents of setting
Operation in parameter
setting mode
Pr.999
*1
10
GOT Initial settings
(PU connector)
[AUTO]
[GOT]
[1]Write
11
GOT Initial settings
(RS-485 terminal)
-
Setting item
*1
Parameter No.
Set value
Contents of
setting
PU
connector
RS-
485
Содержание GT16
Страница 1: ......
Страница 2: ......
Страница 46: ...1 4 1 OVERVIEW 1 1 Features ...
Страница 54: ...2 8 2 SYSTEM CONFIGURATION 2 2 System Equipment ...
Страница 60: ...3 6 3 SPECIFICATIONS 3 4 Battery specifications ...
Страница 72: ...5 8 5 UL cUL STANDARDS AND EMC DIRECTIVE 5 2 EMC Directive ...
Страница 102: ...6 30 6 OPTION 6 7 Connector Conversion Box ...
Страница 106: ...7 4 7 INSTALLATION 7 1 Installing Procedure ...
Страница 110: ...8 4 8 COMMUNICATION CABLE 8 1 Overview of Communication Cable ...
Страница 130: ...9 20 9 HANDLING OF POWER WIRING AND SWITCH 9 4 Switch Wiring ...
Страница 142: ...10 12 10 UTILITY FUNCTION 10 3 Utility Display ...
Страница 184: ...11 42 11 DISPLAY AND OPERATION SETTINGS GOT SET UP 11 4 Maintenance Function ...
Страница 202: ...12 18 12 COMMUNICATION INTERFACE SETTING COMMUNICATION SETTING 12 3 Ethernet Setting ...
Страница 226: ...13 24 13 DEBUG 13 3 Memory Data Control ...
Страница 248: ...14 22 14 SELF CHECK 14 2 Batch Self Check ...
Страница 350: ...15 102 15 DATA CONTROL 15 3 OS Project Information ...
Страница 410: ...19 22 19 TROUBLESHOOTING 19 2 Error Message and System Alarm ...
Страница 418: ...App 8 APPENDICES Appendix 3 Transportation Precautions ...
Страница 422: ...REVISIONS 4 ...
Страница 425: ......
Страница 426: ......
Страница 427: ......
Страница 428: ......
Страница 470: ......
Страница 510: ...21 22 21 COMPUTER LINK CONNECTION 21 6 Precautions ...
Страница 568: ...22 58 22 ETHERNET CONNECTION 22 5 Precautions ...
Страница 584: ......
Страница 626: ...25 14 25 SERVO AMPLIFIER CONNECTION 25 7 Precautions ...
Страница 632: ...26 6 26 ROBOT CONTROLLER CONNECTION 26 6 Precautions ...
Страница 647: ...MULTIPLE GOT CONNECTIONS 29 GOT MULTI DROP CONNECTION 29 1 ...
Страница 648: ......
Страница 659: ...MULTI CHANNEL FUNCTION 30 MULTI CHANNEL FUNCTION 30 1 ...
Страница 660: ......
Страница 675: ...FA TRANSPARENT FUNCTION 31 FA TRANSPARENT FUNCTION 31 1 ...
Страница 676: ......
Страница 742: ...31 66 31 FA TRANSPARENT FUNCTION 31 7 Precautions ...
Страница 744: ......
Страница 766: ...32 22 32 CONNECTION TO IAI ROBOT CONTROLLER 32 7 Precautions ...
Страница 802: ...34 10 34 CONNECTION TO OMRON TEMPERATURE CONTROLLER 34 7 Precautions ...
Страница 834: ...36 18 36 CONNECTION TO KOYO EI PLC 36 6 Device Range that Can Be Set ...
Страница 858: ...38 12 38 CONNECTION TO SHARP PLC 38 6 Device Range that Can Be Set ...
Страница 868: ...39 10 39 CONNECTION TO SHINKO TECHNOS INDICATING CONTROLLER 39 7 Precautions ...
Страница 902: ...42 6 42 CONNECTION TO TOSHIBA MACHINE PLC 42 6 Device Range that Can Be Set ...
Страница 908: ...43 6 43 CONNECTION TO PANASONIC SERVO AMPLIFIER 43 7 Precautions ...
Страница 970: ...48 12 48 CONNECTION TO FUJI TEMPERATURE CONTROLLER 48 7 Precautions ...
Страница 1052: ...52 26 52 CONNECTION TO AZBIL CONTROL EQUIPMENT 52 7 Precautions ...
Страница 1102: ...55 14 55 CONNECTION TO GE PLC 55 7 Precautions ...
Страница 1114: ...57 4 57 CONNECTION TO SICK SAFETY CONTROLLER 57 5 Device Range that Can Be Set ...
Страница 1128: ...59 2 59 CONNECTION TO HIRATA CORPORATION HNC CONTROLLER ...
Страница 1130: ...60 2 60 CONNECTION TO MURATEC CONTROLLER ...
Страница 1131: ...MICROCOMPUTER CONNECTION 61 MICROCOMPUTER CONNECTION SERIAL 61 1 62 MICROCOMPUTER CONNECTION ETHERNET 62 1 ...
Страница 1132: ......
Страница 1270: ...62 68 62 MICROCOMPUTER CONNECTION ETHERNET 62 8 Precautions ...
Страница 1271: ...MODBUS CONNECTIONS 63 MODBUS R RTU CONNECTION 63 1 64 MODBUS R TCP CONNECTION 64 1 ...
Страница 1272: ......
Страница 1292: ...64 12 64 MODBUS R TCP CONNECTION 64 7 Precautions ...
Страница 1293: ...CONNECTIONS TO PERIPHERAL EQUIPMENT 65 VNC R SERVER CONNECTION 65 1 ...
Страница 1294: ......
Страница 1298: ...65 4 65 VNC R SERVER CONNECTION 65 4 Setting in Personal Computer ...
Страница 1302: ...REVISIONS 4 ...
Страница 1305: ......
Страница 1306: ......