OmegaPATPlus / BetaPATPlus Measurements
39
Testing of portable RCD
First connect portable RCD unit into the test socket. Then connect PRCD test probe to
the portable RCD unit and the other end of PRCD probe to the PRCD socket of the
instrument.
6.8.2 How to perform an RCD test
From the
Main menu
, select
Single test
and then select
RCD test
by using
¿
and
À
cursor keys and press ENTER key to confirm.
RCD menu
is displayed.
RCD single test menu
RCD autotest menu
Measurement parameters are detailed in the top right corner of the display. The
following parameters can be adjusted in this measurement:
Ì
nominal test current value,
Ì
test current size (multiplier),
Ì
test current starting polarity,
Ì
test
mode.
To edit the parameters, press the F1 function key first. Use
¿
and
À
cursor keys to
select the parameter you want to edit. By using
½
and
¾
cursor keys adjust the selected
parameter. Press F1 function key again to confirm the selection.
Nominal test current I
Δ
N
The nominal test current can be set to 10mA, 15mA and 30mA. These are the typical
values for portable RCDs.