OmegaPATPlus / BetaPATPlus Instrument description
11
Resistance L – N too
low.
Are you sure to
proceed? (Y/N)
An extremely low resistance of the appliance’ supply input
was measured in the pre-test. It is likely that fuses will
blow after applying power to the tested appliance. If the
too high current is only of short duration (caused by a
short inrush current) the test can be performed otherwise it
must be stopped.
Select
YES
or
NO
with Y or N key.
It is recommended to additionally check the appliance
before proceeding with the test!
Leakage LN-PE high.
Are you sure to
proceed? (Y/N)
Dangerous leakage current (higher than 3.5 mA) will flow if
power would be connected to the tested appliance.
Select
YES
or
NO
with Y or N key.
Proceed with testing only if all safety measures have
been taken. It is recommended to perform a thorough
earth bond test on the PE of the appliance before
proceeding with the test.
Leakage LN-PE too
high.
Are you sure to
proceed? (Y/N)
Dangerous leakage current (higher than 20 mA) will flow if
power would be connected to the tested appliance.
Select
YES
or
NO
with Y or N key.
Proceed with testing only if all safety measures have
been taken. It is recommended to perform a thorough
earth bond test on the PE of the appliance before
proceeding with the test.
Leakage LN-PE or EB-
PE too high!
Are you sure to
proceed? (Y/N)
Dangerous leakage current (higher than 20 mA) will flow if
power would be connected to the tested appliance.
Select
YES
or
NO
with Y or N key.
Proceed with testing only if all safety measures have
been taken. It is recommended to perform a thorough
earth bond test on the PE of the appliance before
proceeding with the test.
Measurement aborted!
Too high leakage
current.
An exceptionally high leakage current (higher than about 5
mA) was measured through PE test terminal or PE socket
during the pre-test or test.