When testing completes, a small message box appears in the middle of the screen showing the progress of the
discharge process (in seconds). When the message disappears, the LEADS ENERGIZED indicator will turn off, and the
test leads will be discharged.
Fig 109:
Auto DC Test completed and displaying discharging message box.
Review the test results here as needed then press the EXIT icon to leave the DC Test screen.
NOTE: If Temperature Compensation is used (set in this screen using the drop-down list, or in the active
test configuration) the MΩ field will display the corrected value based on that compensation, not the
direct calculated value. You can change this display during testing by changing the value in the Temp
Compensation drop-down list.
Before returning to the Automatic Test main menu, a message appears instructing you to allow the asset sufficient time
to discharge before removing test leads. Depending on the asset’s size and the amount of time high voltage has been
applied, this time will vary.
WARNING: To ensure the safety of all personnel, refer to “Ensure Proper Grounding
and Discharge after Conducting DC Tests” in chapter 1, “General Operating and Safety
Information” for guidance on properly discharging and grounding the asset (DUT).
If you plan to continue with Surge testing, no grounding is needed at this time, but do not touch test leads before
testing is properly executed and completed. Grounding should be conducted as needed after completion of all tests.
www.megger.com
Megger Baker ADX User Guide
111
Auto Tests
Содержание ADX15
Страница 1: ...Megger Baker ADX Automated Diagnostic Test Equipment User Guide...
Страница 2: ...www megger com Megger Baker ADX User Guide...
Страница 10: ...www megger com Megger Baker ADX User Guide viii Table of Contents...
Страница 44: ...www megger com Megger Baker ADX User Guide 34...
Страница 84: ...www megger com Megger Baker ADX User Guide 74 Routes...
Страница 148: ...www megger com Megger Baker ADX User Guide 138...
Страница 172: ...www megger com Megger Baker ADX User Guide 162...