MyPower S6600 Series Routing Switch Installation Manual
Installation Preparations
copyright
©
2015 Maipu All rights reserved.
11
select as desired.
�
When using the power surge protector, ensure that the PE terminal is
grounded.
�
After inserting the AC power plug of the switch into the socket of the power
surge protector (lightning connector bar), only the green light indicating
running on the power surge protector is on. When there is no red light for
alarming, regard that the lightning protection is realized.
�
When there is red light for alarming on the power surge protector, pay much
attention and process it. Confirm whether Fire (L), zero (N), ground (PE) wires
are connected correctly. After confirming that the PE connection is correct, you
can detect via the following method: Switch the multimeter to AC, test
whether the voltage between N and PE is smaller than or equal to 5V, and the
voltage between L and PE is about 220V. If not, indicate that the fire wire and
zero wire are connected reversely.
3.3.2
3.3.2
3.3.2
3.3.2
Install
Install
Install
Install Network
Network
Network
Network Port
Port
Port
Port Surge
Surge
Surge
Surge Protector
Protector
Protector
Protector
If there is outdoor network cable connected to the switch when using the switch,
it is suggested to connect the network port surge protector in series first before
the network cable is connected to the switch interface, so as to reduce the
probability of damaging the switch caused by the lightning.
The steps of installing the network port surge protector:
Step 1:
According to the distance of the switch ground terminal or the lightning grounding cooper
bar of the machine room, shorten the ground wire of the network port surge protector, and
tighten the ground wire of the network port surge protector to the ground terminal of the
switch or the lightning grounding cooper bar of the machine room tightly.
Step 2:
Use the multimeter to measure whether the ground wire of the surge protector is well
contacted with the ground terminal of the switch or the lightning grounding cooper bar of
the machine room.
Step 3:
According to the description in the user manual of the network port surge protector, connect
the network port surge protector via the network port transit cable (pay attention to the
direction: connect the external cable to the IN end and connect the transit cable connected
to the switch to the OUT end). Meanwhile, check whether the display of the board indicator
is normal.
Step 4:
Use the cable tie to bind up the cables.