The AC power supply system of the communication equipment room
should adopt the TN-S power supply mode.
2
At the entrance of the AC power wire entering the equipment room,
we should configure the AC power mine (C-class mine) with the
discharge current no less than 20KA.
3
The protection ground of the communications power should share
one group of ground body with the protection ground of the
communication device. When the communication power and the
communication device are at the same equipment room, they should
share the protection ground bar of the same equipment room.
4
AC power port should be added with lightning protection circuit.
5
The positive polarity of -48V DC power (or the negative polarity of
the 24V DC power) should be grounded at the DC power output site.
6
The working ground and PGND of the DC power should share the
same grounding body with the AC device PGND. When the
communication power and the communication device are in the
same equipment room, it is recommended for them to share the
same protection grounding bar in the same equipment room.
7
The DC power port should add surge protection circuit.
E1.5
E1.5
E1.5
E1.5 Laying
Laying
Laying
Laying Specifications
Specifications
Specifications
Specifications of
of
of
of Ground
Ground
Ground
Ground Wires
Wires
Wires
Wires
The laying specifications of the ground wire are as shown in appendix table E-4:
A
A
A
A
P P E N D I X
P P E N D I X
P P E N D I X
P P E N D I X T A B L E
T A B L E
T A B L E
T A B L E
E
E
E
E
4
4
4
4 L
L
L
L
A Y I N G
A Y I N G
A Y I N G
A Y I N G S P E C I F I C A T I O N S
S P E C I F I C A T I O N S
S P E C I F I C A T I O N S
S P E C I F I C A T I O N S O F
O F
O F
O F G R O U N D
G R O U N D
G R O U N D
G R O U N D W I R E
W I R E
W I R E
W I R E
No.
No.
No.
No.
Description
Description
Description
Description
1
Ground lead should not be intertwined or parallel with the signal line.
2
Grounding cable cannot be led aerially, but should be buried in the
earth or routed indoor.
3
On the protection ground wire, prohibit the connectors; prohibit
installing the switch or fuse.
4
The protection ground wire should adopt the yellow and green plastic
insulated copper wire.
5
The neutral line of the AC power cable in the equipment room cannot
be connected with the protection ground of the transmission and
communication devices in the equipment room.