3.0 Setup
Info:
The voltage settings shown in Table 3-1 are based on the
Battery Temperature Sensor (BTS) having been at a temperature
of 77° F (25° C), or not connected. If the BTS is connected, the
actual charge voltage will increase if the temperature around
the BTS is below 77° F (25° C), and decrease if higher than 77°
F (25° C). This ensures the batteries receive the correct charge
voltage regardless of temperature.
Table 3-1, Battery Type to Charge Voltages
Battery
Type
Inverter
Voltage
Absorption
Voltage
Float
Voltage
Equalization
Voltage
GEL
12 VDC
14.1 VDC
13.6 VDC
14.1 VDC
1
24 VDC
28.2 VDC
27.2 VDC
28.2 VDC
1
48 VDC
56.4 VDC
54.4 VDC
56.4 VDC
1
Flooded
12 VDC
14.6 VDC
13.4 VDC
15.5 VDC
24 VDC
29.2 VDC
26.8 VDC
31.0 VDC
48 VDC
58.4 VDC
53.6 VDC
62.0 VDC
AGM 1
2
12 VDC
14.3 VDC
13.1 VDC
15.5 VDC
24 VDC
28.6 VDC
26.2 VDC
31.0 VDC
48 VDC
57.2 VDC
52.4 VDC
62.0 VDC
AGM 2
3
12 VDC
14.5 VDC
13.5 VDC
14.5 VDC
1
24 VDC
29.0 VDC
27.0 VDC
29.0 VDC
1
48 VDC
58.0 VDC
54.0 VDC
58.0 VDC
1
Custom
4
12 VDC
12.0-16.0 VDC 12.0-16.0 VDC
12.0-16.0 VDC
24 VDC
24.0-32.0 VDC 24.0-32.0 VDC
24.0-32.0 VDC
48 VDC
48.0-64.0 VDC 48.0-64.0 VDC
48.0-64.0 VDC
Note 1: Voltage same as absorption voltage – to prevent equalization.
Note 2: Specifi cations for Concord (Lifeline Series) AGM batteries.
Note 3: Specifi cations for East Penn, Deka, Discover and Trojan AGM batteries.
Note 4: When using the Custom setting, the EQ (Equalization) voltage
adjustment cannot be set lower than the Absorb Voltage setting. Also, the
EQ Voltage adjustment cannot be set higher than 2-volts (12-volt systems),
4-volts (24-volt systems), or 8-volts (48-volt systems) above the Absorb
voltage setting.
03C Max Charge Rate:
Sets the maximum charge rate allowed to
charge the batteries during Bulk, Absorption, Float, and Equalize
charging. Selections are
Max Charge = 0%
up to
Max Charge = 100%
.
The
Max Charge = 0%
setting is available to help minimize charging
while continuing to allow pass-through power. The rest of the selections
are provided to limit the charge rate to the battery bank, which helps
prevent battery overheating caused by charging at too high a charge rate.
The maximum charge selections are provided as a percentage of the
inverter/charger’s maximum charging capability. Refer to the label on
the side of the inverter or the owner’s manual for the inverter/charger
to determine its maximum charge rate. Once you
fi
nd this maximum
charge rate, determine the percentage needed to limit the charge rate
to your battery bank.
•