3.0 Setup
3.2.4.1 Accessory Setup
The
AGS Setup
and
BMK Setup
menus only display if the related accessory
is connected to the router’s inverter/charger, or is directly connected to the
router and has been assigned to one of the router’s communication ports.
The
REM Setup
menu only displays if the remote is connected and assigned
to a communication port on the router.
Unlike the previous SETUP menu items, the accessory SETUP menus are
accessed through the System Home screen and the PORT button.
To access the SETUP menus for an accessory:
Display the System Home screen (press the METER button for 3-seconds):
Press the PORT button until: a) you
fi
nd the port (P#) to which the
accessory is connected to the router; or, b) you
fi
nd the port (P#Acc)
to which the accessory is connected to an inverter.
Press the SETUP button. The accessory’s SETUP menu appears.
Use the SELECT knob to navigate the menus and to make adjustments
for that accessory.
04 AGS Setup
This menu is used to set up the functions related to the ME-AGS-N (Automatic
Generator Start - Network version). These functions automatically start and
stop the generator based on the following conditions:
04A Gen Run VDC:
Starts/stops based on battery voltage as shown on
the System Home screen.
04B Gen Run Time:
Starts/stops based on time of day. This feature
uses the router clock to determine start and stop times.
04C Gen Run Amps:
Starts/stops based on the AC amp load on the
inverter while in Invert mode. When the AGS is connected directly to the
router, the AGS starts/stops based on the total AC amp load of all the
inverters in the parallel system (while inverting). When the AGS is directly
connected to an inverter, the AGS starts/stops based on that inverter’s
AC amp load (while inverting). The AC amp load value is determined from
the
02C Load Amps
menu item
(METER button’s
AC Meters
menu).
04D Gen Run SOC:
Starts/stops based on the SOC reading from the BMK.
The AGS uses the SOC value as shown on the System Home screen to
determine when start/stop. If multiple BMK’s are installed in the system,
the System Home screen will display the SOC value of the BMK that is
connected to the lowest numbered port.
Example:
An inverter connected to Port 2 has a BMK connected to
its Network port; this BMK is designated as “
P2ACC
”. A second BMK is
connected directly to Port 3 on the router and is designated as “
P3
”. The
System Home screen will display the SOC value from the BMK designated
as
P2ACC
.
04E Gen Run Temp:
Starts based on the interior temperature or the
A/C thermostat as determined by the AGS temperature sensor, and stops
after the Gen Run Time setting is completed.
Info:
For detailed information on the ME-AGS-N and all its
menus, refer to it’s owner’s manual (PN: 64-0039).