5.0 Operation
5.3.3 AC In Control Status Messages
These displays alternate with the inverter/charger status to indicate that
there is AC power present at the AC input, but the inverter/charger is not
connecting to the incoming power.
VDC Connect
- The DC battery voltage needs to fall below the
Set
Connect Volts
setting in the
02D AC IN VDC
menu in order for the inverter/
charger to reconnect to incoming AC.
Time Connect
- The time of day needs to fall within the
Set Connect
Time
setting per the
02C AC In - Time
menu in order for the inverter/charger
to reconnect to incoming AC.
AC In - Disabled
- The inverter/charger is being prevented from
reconnecting to any incoming AC.
5.3.4 Fault Mode Messages
The FAULT LED comes on and a fault status is displayed when an abnormal
condition is detected. Use the information in this section to determine and
correct the issue.
Info:
Many of the faults will automatically restart when the fault
is cleared. Some will require a manual restart. This requires
the ON/OFF INVERTER button on the router to be pressed and
released. Finally, if the fault will not clear, an inverter reset may
be required – see Section 6.2 to perform an inverter reset.
•
•
•
FAULT
PWR
CHG
INV
VDC Connect
Settings/Info...
VDC Connect
appears on LCD. PWR
(green) is on solid and CHG (green)
is blinking.
Figure 5-15, VDC Connect Mode
Time Connect
appears on LCD. PWR
(green) is on solid and CHG (green)
is blinking.
FAULT
PWR
CHG
INV
Time Connect
Settings/Info...
Figure 5-16, Time Connect Mode
FAULT
PWR
CHG
INV
AC In - Disabled
Settings/Info...
AC In - Disabled
appears on LCD.
PWR (green) is on solid and CHG
(green) is blinking.
Figure 5-17, AC In - Disabled Mode