© 2010 Magnum Energy, Inc.
40
3.0 Setup
Info:
When the router is connected to inverters that are stacked
in parallel or series, there will be a stacking indication following
the model number. The indications will indicate the following
stacking conditions: “
PM”
- Parallel Master; “
PS”
- Parallel Slave;
“
SM”
- Series Master; “
SS”
- Series Slave.
Info:
The
BMK, AGS, and the remote accessories may display
a “
0.0
” revision for several reasons. Either the accessory is not
installed, there is no communication because of a bad or miswired
network cable, the device is not powered, or the device is bad.
Firmware Versions (TECH 03):
The
Firmware Versions (Acc Port)
menu
displays all the accessories connected to the router. The accessory versions
display in the order of the port to which they are connected (1-6).
Fault History (TECH 04):
This menu shows a two screen display for each
history of the last 9 inverter faults. Information for each fault displays
from the most recent fault (H1) to the earliest fault (H2 up to H9).
Info:
All recorded fault history displays will be retained (except
for the day the fault occurred), even if power is removed from
the router.
Info:
All recorded fault history information can be cleared by
going to the Fault History front screen (display shows “Fault
History\Press Select to View\Tech 04”). Once this screen displays,
press and hold the SELECT knob for ~ 5 seconds until the screen
displays “No Faults Recorded\Tech 04”.
•
•
H1 Low Battery
BTS 25C Tfmr 45C
FETs 40C
P1 3 12 :00a Tech 04
Port
Days since fault
Time
Menu
Fault Mode
Transformer,
Battery , and FET
Temps
Fault History Number
H1 Low Battery
Inverting
21 .0Vdc 12Adc
P1 3 12 :00a Tech 04
Port
Days since fault
Time
Menu
Fault Mode
DC Battery Voltage
Status
DC Amps
Fault History Number
Figure 3-8, Fault History (fi rst and second screens)
Figure 3-8 - first screen (left graphic): The top line displays the fault history
number and the fault mode. The second line displays the status of the inverter/
charger at the time of the fault. The third line displays DC battery voltage
and amperage readings at the time of the fault. The bottom line displays the
port that the fault occurred at, how many days ago the fault occurred, the
time of the fault, and the menu in which it occurred.
Figure 3-8 - second screen (right graphic): The top line displays the fault
history number and the fault mode. The second and third line display
transformer, battery, and FETs temperatures at the time of the fault. The
bottom line displays the port that the fault occurred at, how many days ago
the fault occurred, the time of the fault, and the menu in which it occurred.