3.0 Setup
01 AC In Control
The
01
AC In Control
menu has four different conditions in which the
inverter/charger will connect to incoming AC power. Only one condition may
be selected at any one time – multiple conditions can be enabled, but only
one can be active.
Info:
Before the inverter allows the AC input to connect to the
AC source (grid or gen), the incoming AC must be qualified by
the inverter/charger (voltage is below the high AC input require-
ments, above the
VAC Dropout
setting, and between 50 Hz to
70 Hz for domestic models – 40-60 Hz for export models).
Info:
The top status line of the LCD display alternates the
inverter/charger status with a secondary
AC IN status when
AC is present, but is
not
connecting as a result of a selection
made in the SETUP menu.
Auto Connect:
Automatically connects to incoming AC power.
VDC Connect:
Connects to incoming AC when the DC battery voltage
is below the
Set Connect Volts
setting in the
02D AC IN VDC
menu.
Disconnects from incoming AC when the DC battery voltage is above the
Set Disconnect Volts
setting, also in the
02D AC IN VDC
menu.
Info
: See SETUP menu 02D on page 28 for a complete
explanation of the
Set Connect Volts
setting.
Time Connect:
Connects to incoming AC when the time of day is between
the
Set
Connect Time
and
Set
Disconnect Time
settings per the
02C AC
In - Time
menu.
Info
: See SETUP menu 02C on page 27 for a complete
explanation of the
Set Connect Hour/Minute/AM-PM
setting.
AC In - Disabled:
Disconnects incoming AC when selected. This setting
will prevent incoming AC from connecting to the inverter/charger.
Example:
AC is present, but
Time Connect
has been selected from the
01 AC In Control
menu, and the current time of day is 6PM. The
02C AC
In-Time
menu’s current setting is 2AM - 8AM. The current time of 6PM is
outside the connect time, so the inverter/charger will not connect to the
incoming AC until after 2AM. The primary
status will display “
Inverting
”
and the secondary
status will display “
Time Connect
” to let you know the
reason that incoming AC has not connected.
•
•
•
•