Feet
Feet
Tab
Step 5.
To reinstall the feet in the location, push the tab of the feet into the right place of the server.
Removing the air baffle
Use this information to remove the air baffle from the server.
Read the safety information in “Safety” on page v and “Installation guidelines” on page 29.
If you are replacing a server component in the server, you need to turn off the server and peripheral devices,
and disconnect the power cords and all external cables.
Attention:
The server automatically powers off when the air baffle is removed.
To remove the air baffle, complete the following steps.
Step 1.
Carefully turn the server on its side so that it is lying flat, with the cover facing up.
Attention:
Do not allow the server to fall over.
Step 2.
Unlock and remove the left-side cover (see “Removing the left-side cover” on page 182).
Step 3.
Press the release latches on both sides of the air baffle, and pull the air baffle up from the server
and set it aside.
188
System x3500 M5 Installation and Service Guide
Содержание System x3500 M5 Type 5464
Страница 1: ...System x3500 M5 Installation and Service Guide Machine Type 5464 ...
Страница 6: ...iv System x3500 M5 Installation and Service Guide ...
Страница 16: ...xiv System x3500 M5 Installation and Service Guide ...
Страница 140: ...124 System x3500 M5 Installation and Service Guide ...
Страница 194: ...178 System x3500 M5 Installation and Service Guide ...
Страница 1056: ...1040 System x3500 M5 Installation and Service Guide ...
Страница 1214: ...1198 System x3500 M5 Installation and Service Guide ...
Страница 1218: ...1202 System x3500 M5 Installation and Service Guide ...
Страница 1225: ...People s Republic of China Class A electronic emission statement Taiwan Class A compliance statement Appendix E Notices 1209 ...
Страница 1226: ...Taiwan BSMI RoHS declaration 1210 System x3500 M5 Installation and Service Guide ...
Страница 1235: ......
Страница 1236: ......