9 Defects and faults
The control circuit for the conveyor sys-
tem is not working.
There is a connection fault.
Check the pull-rope emergency stop
switch connection
„Electrical connection", page 24)
.
A switching element (
6
)
N/O contact
is
defective.
Check that switching element (
6
)
N/O
contact is working properly (see
Section 5.2.4, step10)
.
If a switching element (
6
)
N/O contact
is
defective, replace the pull-rope emer-
gency stop switch
„Mounting and dismounting", page 31)
The pull-rope emergency stop switch is
not triggered with the pull-rope mounted
on one side.
The trigger lever (
1
) is stiff or blocked.
Carry out a function test
.
Defect / fault
Cause
Remedy