2. Press the «Right» arrow.
3. Press «Enter».
The control field
Logic flashes.
4. Use «UP» or «Down» to set the desired behaviour, see table 82.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.10.2.1 External message 1
Menu
External message 1
Message text
DI1.07
ok ☑
Input selected
td:
0s ¦ Logic :
+
active line, set logic control field
DOR1.04
☐
Warning
☑
Message type (operational, alarm, warning)
5. Press «Enter».
Result For messages at 24 V, the logic is set with the + symbol.
8.8.2.6 Setting the message type
1. Select the message type line with the «Up» and «Down» keys.
2. Press «Enter».
The display for the message type flashes.
3. Use «Up» or «Down» to set the message type.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.10.2.1 External message 1
Menu
External message 1
Message text
DI1.07
ok ☑
Input selected
td:
0s ¦ Logic :
+
DOR1.04
☐
Warning
☑
Example: Warning message type
4. Press «Enter».
The message type is set.
8.8.2.7 Assign and activate the output
1. Use «Up» or «Down» to select the
DOR line.
2. Press «Enter».
The
DOR output display flashes.
3. Select the output with the «Up» and «Down» keys.
8
Initial Start-up
8.8
Setting input and output signals
No.: 901700 14 E
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
127