Machine number
Start time [sec]
Delay time [sec]
6
7
8
9
10
11
12
13
14
15
16
Tab. 64 Delay time for automatic restart
Precondition Access level 2 is activated.
1. Open the 5.3
<Configuration – Restart> menu.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.3 Restart
Menu
Automatic restart
☐
Automatic restart is deactivated
Delay
1s
Set/expiring delay time
2. Use «Up» or «Down» to select the
Delay line.
3. Press «Enter».
The setting mode is active.
4. Use «Up» or «Down» to set the delay time value.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.3 Restart
Menu
Automatic restart
☐
Automatic restart is deactivated
Delay
10 s
Set/expiring delay time
5. Press the «Enter» key.
The setting is applied.
Result You have adjusted the delay tome for the restart after a power supply failure from 1 s to 10 s.
8
Initial Start-up
8.5
Machine start and machine stop
No.: 901700 14 E
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
87