Message
Possible cause
Remedy
0201 W
Change belt h ↑
V-belt:
Maintenance interval expired.
Contact an authorised service
partner.
0202 W
Change filter h ↑
Inlet filter:
Maintenance interval expired.
Replace inlet filter.
0203 W
Change filter mat h ↑
Air filter:
Maintenance interval expired.
Change filter mat.
0204 W
Motor bearings lube h ↑
Drive motor bearings:
Maintenance interval expired.
Relubricate drive motor bear‐
ings.
0205 W
Check motor bearings h
↑
Check drive motor bearings.
Check drive motor bearings.
0206 W
Change motor bearings
h ↑
Drive motor bearings:
Maintenance interval expired.
Contact an authorised service
partner.
0207 W
Check motor bearings
encl. fan h ↑
Sound enclosure fan motor bearings:
Maintenance interval expired.
Contact an authorised service
partner.
0208 W
Check control cabinet
fan h ↑
Control cabinet fan motor bearings:
Maintenance interval expired.
Contact an authorised service
partner.
0209 W
Check FC fan h ↑
Frequency converter fan motor bear‐
ings:
Maintenance interval expired.
Contact an authorised service
partner.
0210 W
Annual maintenance due
Last maintenance was 1 year ago.
Carry out the necessary main‐
tenance tasks and reset the
corresponding maintenance
counters.
0211 W
Filter change
transmission venting h ↑
Maintenance interval expired
Change the filter
0212 W
Electrical equipment h ⇞
Maintenance interval expired
Carry out the necessary main‐
tenance tasks and reset the
corresponding maintenance
counters.
0220 W
External counter 1
1)
0221 W
External counter 2
1)
0222 W
External counter 3
1)
0300 W
SD card write error
Fault while writing data to SD card.
Contact an authorised service
partner.
0868 W
AII%d.0%d - open circuit
Wire break in line for ext. sensor at an‐
alogue input.
Check line paths and sensor
connection.
0869 W
AII%d.0%d - short-circuit
Short circuit in line for ext. sensor at
analogue input.
Check line paths and sensor
connection.
10 Fault Recognition and Rectification
10.3 Interpreting warning messages
164
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
No.: 901700 14 E
Содержание SIGMA CONTROL 2
Страница 2: ...KKW SSC 2 15 en IBA SIGMA CONTROL BLOWER KKW SSC 2 15 20220810 080650...
Страница 8: ...List of Illustrations vi Service Manual Controller SIGMA CONTROL 2 BLOWER 4 0 X No 901700 14 E...
Страница 12: ...List of Tables x Service Manual Controller SIGMA CONTROL 2 BLOWER 4 0 X No 901700 14 E...