2. Use «Up» or «Down» to select the
Acknowledge messages line.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.5 External DI / AII signal
Menu
Idle signal
DI1.09
☐
······························
Acknowledge messages
DI1.05
☐
······························
3. Press the «DOWN» key.
The input
DI has been selected.
4. Press «Enter».
The display for the currently set input flashes.
5. Select the input DI1.05 with the «Up» or «Down» key.
6. Press the «Enter» key.
The setting is applied.
7. Press the «Right» key.
8. Press «Enter».
The check box assigned to the input flashes.
9. Press the «Up» key.
The check box is activated.
10. Press «Enter».
The setting is applied.
ok is displayed.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.5 External DI / AII signal
Menu
Idle signal
DI1.09
☐
······························
Acknowledge messages
DI1.05
ok ☑
Active line with deactivated check box
······························
Result The Remote acknowledgement function is activated.
Activating the remote control
➤ Activate remote control see chapter 8.2.13.
Result The remote control is activated.
Result Should a message occur, it can now be acknowledged from a control centre.
8
Initial Start-up
8.9
Activating remote acknowledgement
No.: 901700 14 E
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
133