10. Press the «Enter» key.
The setting is applied accordingly.
ok is displayed.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.5 External DI / AII signal
Menu
▶1 Current signal AII1.02
Blower on
DI1.05
ok ☑ Logic :
+
Active line
······························
Load signal
DI1.09
☐ Logic :
+
11. Press the «Escape» key repeatedly to exit the menu.
Result The blower is set to remote operation.
8.5.4.2 Setting the load signal to remote operation
Precondition Electrical connection via DI 1.04 – terminal -X15: 5+6 is established
Access level 2 is activated
The operating mode is displayed
1. Open the menu 5.5
<Configuration – External DI / AII signal>.
2. Using the «Up» or «Down» key, select the line
Load signal.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.5 External DI / AII signal
Menu
Load signal
Active line
DI1.04
☐ Logic :
+
······························
Idle signal
DI1.09
☐ Logic :
+
······························
3. Press the «Down» key.
The input
DI has been selected.
4. Press the «Enter» key.
The display flashes for the input currently set.
5. Using the «Up» or «Down» key, select the input DI1.04.
6. Press the «Enter» key.
The setting is applied accordingly.
7. Press the «Right» key.
8. Press the «Enter» key.
The check box assigned to the input flashes.
9. Press the «Up» key.
The check box is activated.
8
Initial Start-up
8.5
Machine start and machine stop
90
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
No.: 901700 14 E