Fig. 40 PROFINET communication module – LEDs and interface
1
Communications module
2
LED NS: Network status
3
LED MS: Module status
4
PROFINET Port 1
5
PROFINET Port 2
6
LED connection status Port 1
7
LED connection status Port 2
LED Colour State
Meaning
2
NS
off
Offline
■ Module without voltage
■ No communication with the IO controller
Green illuminates continuously Online (RUN)
■ Module connected to bus, communication is running
■ IO controller in RUN mode
flashes
Online (STOP)
■ Module connected to bus, communication is running
■ IO controller in STOP mode
3
MS
off
Not initialised
■ Module without voltage
■ Module in "Setup" status
■ Module in "NW-INIT" status
Green illuminates continuously Module in operation
flashes 1:1 (on:off)
Diagnostic data available
flashes 2:1 (on:off)
Is used by Engineering Tools to identify the network node
Red
illuminates continuously Module in "EXCEPTION" status
flashes 1:1 (on:off)
Configuration fault
flashes 2:1 (on:off)
IP address not set
flashes 3:1 (on:off)
Station name not set
flashes 4:1 (on:off)
Internal error
6
,
7
off
No connection.
Green illuminates continuously Connection established, no communication
flashes
Communication in operation
Tab. 94 PROFINET communications module – Interpretation of LEDs
9
Operation
9.9
Communication modules
152
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X