1. Open the 3.1
<Operating data – Operating hours> menu.
The
Operating hours menu is displayed.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
3.1 Operating hours
Menu
Blower package
3050h
active line
On load
3050h
Motor
3050h
Block
3050h
SIGMA CONTROL 2
3050h
FC block drive
3050h
Changing the operating hours
You can adjust the running times of the drive motor (Motor) and the compressor. This may be re‐
quired after a replacement, for example.
Precondition Access level 2 is activated
1. Open the menu 3.1
<Operating data – Operating hours>.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
3.1 Operating hours
Menu
Blower package
3050h
On load
3050h
Motor
3050h
active line
Block
3050h
SIGMA CONTROL 2
3050h
FC block drive
3050h
2. Using the «Up» or «Down» key, select the line
Motor.
3. Press the «Enter» key.
The display of the running time flashes (e.g.,
3050 h).
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
3.1 Operating hours
Menu
Blower package
3050h
On load
3050h
Motor
0h
active line
Block
3050h
SIGMA CONTROL 2
3050h
FC block drive
3050h
4. Use «Down» or «Up» key to set the value for operating hours to zero.
5. Press the «Enter» key.
The setting is applied accordingly.
6. Press the «Escape» key repeatedly to exit the menu.
Result The operating hours for the new drive motor are set to
0 h.
9
Operation
9.6
Displaying operating data
144
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
No.: 901700 14 E