Precondition Access level 2 is activated
1. Open the menu 5.1
<Configuration – General>.
2. Using the «Up» or «Down» key, select the line
Display illumination.
3. Press the «Down» key.
The line
Mode is displayed.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.1 General
Menu
······························
Pressure unit
bar
Unit of pressure
Temperature unit
°C
Unit of temperature
······························
Display illumination
Mode
auto.¦
Timeout:
1min
Active line
4. Press the «Enter» key.
The indicator for the specified mode flashes.
5. Use the «Up» or «Down» key to set the
auto. mode.
6. Press the «Enter» key.
The setting is applied accordingly.
7. Press the «Right» key.
8. Set the value for the
Timeout in the same way: e.g. 1 min.
9. Press the «Enter» key.
10. Press the «Escape» key repeatedly to exit the menu.
Result The display illumination is set to automatic mode, with deactivation after one minute in the absence
of any key being pressed.
8.2.12 Setting the contrast and the brightness
Contrast and brightness are factory set to normal light conditions. You can manually set contrast
and brightness for different lighting conditions.
Precondition The operating mode is displayed.
1. Press and hold the «Information» key.
2. Use «Up» or «Down» to set the contrast.
3. Use «Left» or «Right» to set the brightness.
Result Contrast and brightness are set.
8.2.13 Activating the remote control
The «remote control» key on the operating panel of the SIGMA CONTROL 2 can be activated or
deactivated. Various menus offer check boxes for this setting.
Precondition Access level 2 is activated.
The operating mode is displayed.
1. Open the menu, e.g. 8
Communication menu.
8
Initial Start-up
8.2
Setting the controller
No.: 901700 14 E
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
61