1. Open the 5.5.1
<Configuration – External DI / AII signal – Current signal AII1.02 > menu.
2. Use «Up» or «Down» to select the
AII1.02 line.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.5.1 Current signal AII1.02
Menu
AII1.02
☐
Active line
Value type
Other
Decimal places
1
Unit
bar
4mA
0.40bar
20mA
1.0bar
3. Press «Enter».
The check box
AII1.02 will flash.
4. Press the «Up» key.
The check box is activated.
5. Press «Enter».
The setting is applied.
6. If necessary, specify settings for
Value type, Decimal places, Unit, Scaling 4mA / 20mA.
7. Press «Escape» repeatedly to leave this menu.
Result The function
Current signal AII1.02 is activated. The machine can be controlled by an analogue
current signal at the AII1.02 input.
8.6.2 Setting the operating mode
Precondition Access level 2 is activated.
The operating mode is displayed.
AII1.02 current signal is set, see chapter 8.6.1
1. Open the 5.4
<Configuration – Operating modes> menu.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.4 Operating modes
Menu
Fixed speed
Currently set operating mode
------------------------------
▶1 Fixed speed
Submenu
▶2 Pressure control
Submenu
▶3 External values control
Submenu
------------------------------
2. Use «Up» or «Down» to select the topmost line.
3. Press «Enter».
The setting mode is active.
The currently set language flashes.
4. Use «Up» or «Down» to set the required operating mode.
5. Press «Enter».
The setting is applied.
8
Initial Start-up
8.6
Operating modes in frequency-controlled machines
94
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
No.: 901700 14 E