9.9.6 Displays at the EtherNet/IP-Module
The communication module features LEDs providing information about the module status.
Fig. 41 EtherNet/IP communication module – LEDs and interface
1
Communications module
2
LED NS: Network status
3
LED MS: Module status
4
EtherNet/IP Port 1
5
EtherNet/IP Port 2
6
LED connection status Port 1
7
LED connection status Port 2
LED Colour State
Meaning
2
NS
off
Module without voltage or IP address not available
Green illuminates continuously Module in operation, connection has been made
flashes
Module waits for connection
Red
illuminates continuously Duplicate IP address or internal fault
flashes
Monitoring time exceeded (time-out)
3
MS
off
Module without voltage
Green illuminates continuously Module in operation, master communicates (scanner in
run status)
flashes
Module not configured or master in idle (scanner in idle
status)
Red
illuminates continuously Internal fault, module in "EXCEPTION" status
flashes
The currently used settings do not correspond to the
saved settings
6
,
7
off
No connection.
Green illuminates continuously Connection established, 100 Mbit/s
flashes
Communication running, 100 Mbit/s
Yellow illuminates continuously Connection established, 10 Mbit/s
flashes
Communication running, 10 Mbit/s
Tab. 95 EtherNet/IP communication module – Interpretation of LEDs
9.10 Save data
SIGMA CONTROL 2 settings can be backed up to an SD card.
9
Operation
9.10 Save data
No.: 901700 14 E
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
153
Содержание SIGMA CONTROL 2
Страница 2: ...KKW SSC 2 15 en IBA SIGMA CONTROL BLOWER KKW SSC 2 15 20220810 080650...
Страница 8: ...List of Illustrations vi Service Manual Controller SIGMA CONTROL 2 BLOWER 4 0 X No 901700 14 E...
Страница 12: ...List of Tables x Service Manual Controller SIGMA CONTROL 2 BLOWER 4 0 X No 901700 14 E...