8.7.1.1 Priorities in master control operation
These priorities are valid in master control operation:
■ Bus (top priority)
■ External contacts (load contact)
■ Master/slave operation
■ Timer control (lowest priority)
8.7.2 SAM 4.0 mode
You must modify the settings in SIGMA CONTROL 2 for the operation via SIGMA NETWORK us‐
ing, for example, the KAESER SIGMA AIR MANAGER 4.0 (SAM 4.0).
Precondition SIGMA CONTROL 2 is connected to SAM 4.0 via SIGMA NETWORK and ready for operation (see
the SAM 4.0 operating manual in the chapter “Installation”)
Network pressure pB is set as the pressure for the “SAM 4.0 manual mode".
Access level 2 is activated.
The remote control is activated (see chapter 8.2.13)
Setting the IP configuration
1. Open the 8.1.1
<Communication – Ethernet/SIGMA NETWORK – IP configuration> menu.
2. Use «Up» or «Down» to select the
IP address line.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
8.1.1 IP configuration
Menu
IP address
169.254.100.103
active line, factory setting
Subnet mask
255.255.000.000
Gateway
169,254,100.97
DNS Server 1
169,254,100.97
DNS Server 2
169,254,100.97
Restart network
☐
3. Set the IP address for SIGMA CONTROL 2 using the following pattern:
169.254.100.(SAM 4.0 machine 102)
(for the setting see chapter 8.2.14).
Setting SAM 4.0 mode
The IP address for SAM 4.0 has been set on SIGMA CONTROL 2 at the factory:
169.254.100.100 and must not be changed. The same applies to Port 2000.
1. Open the 8.1.2.2
<Communication – Ethernet/SIGMA NETWORK – Connections – SAM 4.0>
menu.
8
Initial Start-up
8.7
Setting the machine for master control operation
106
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
No.: 901700 14 E