Parameters
Factory setting
Set value
Timeout
5 s
Monitoring
Check box ☑ activated
Tab. 71 Setting the
Timeout parameter
➤ Enter the required settings, as described above.
8.7.3.4 Commissioning the Modbus TCP module
Machine
Precondition Access level 2 is activated.
The network parameters are known. Request the required information from your IT department
1. Open the 8.2
<Communication – Com-Module> menu.
2. Activate the
Com-Module Start check box.
The communication module is activated. The system detects the communication module type
and displays it in the
Type line.
3. Select the data exchange direction:
► SIGMA CONTROL 2 ⇆ Bus master (SIGMA CONTROL 2 sends process data and receives
control data):
Send/Receive or Master: Set Com module.
► SIGMA CONTROL 2 → Bus master (SIGMA CONTROL 2 sends process data):
Send or
Master: Setting SAM/JSON-RPC.
4. Set the required reaction in the event of a bus fault (see next chapter, “Reaction in a PROFI‐
BUS bus fault”).
5. Set IP-Parameter as described below.
Use DHCP
Do not use DHCP
1. Activate the
DHCP check box.
2. Activate the
Use IP settings check box to
apply the IP-Parameter.
The communication module is started with
the set parameters.
Communication with the bus master is run‐
ning.
Time-out at bus fault is activated.
Bus communication is now monitored. The
number behind
Status Counter (Run) con‐
tinuously changes during communication.
1. Deactivate the
DHCP check box.
2. Set
IP address.
3. Set
Subnet mask.
4. Set the
Gateway address.
5.
DNS Server 1-Setting address (optional).
6.
DNS Server 2-Setting address (optional).
7. Activate the
Use IP settings check box to
apply the IP-Parameter.
The communication module is started with
the set parameters.
Communication with the bus master is run‐
ning.
Time-out at bus fault is activated.
Bus communication is now monitored. The
number behind
Status Counter (Run) con‐
tinuously changes during communication.
Reaction in a bus fault
Only for machines.
8
Initial Start-up
8.7
Setting the machine for master control operation
112
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X