7. Press the «Up» key.
The check box is activated.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.10.2.1 External message 1
Menu
External message 1
Message text
DI1.07
ok ☑
Input selected
td:
0s ¦ Logic :
+
Logic
DOR1.04
☐
Warning
☑
Message type (operational, alarm, warning)
8. Press «Enter».
ok is displayed.
The input is assigned and activated.
8.8.2.4 Set the time delay
The delay can be set between 0 and 600 seconds. The delay is counted down from 600 in 1
second increments with the «DOWN» key and counted upwards from 0 (zero) in 1 second
increments with the «UP» key.
1. Use «Up» or «Down» to select the
td line.
2. Press «Enter».
The
td delay time flashes.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.10.2.1 External message 1
Menu
External message 1
Message text
DI1.07
ok ☑
Input selected
td:
0s ¦ Logic :
+
set time delay td
DOR1.04
☐
Warning
☑
Message type (operational, alarm, warning)
3. Use «Up» or «Down» to set the time delay in seconds.
4. Press «Enter».
Result The
td delay time has been set.
8.8.2.5 Setting the logic
Possible logic settings
Message at
Sign
24 V
+
0 V
-
Tab. 82 Logic settings
1. Use «Up» or «Down» to select the
td line.
8
Initial Start-up
8.8
Setting input and output signals
126
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
No.: 901700 14 E
Содержание SIGMA CONTROL 2
Страница 2: ...KKW SSC 2 15 en IBA SIGMA CONTROL BLOWER KKW SSC 2 15 20220810 080650...
Страница 8: ...List of Illustrations vi Service Manual Controller SIGMA CONTROL 2 BLOWER 4 0 X No 901700 14 E...
Страница 12: ...List of Tables x Service Manual Controller SIGMA CONTROL 2 BLOWER 4 0 X No 901700 14 E...