![Jung Smart Control SC 1000 KNX Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/jung/smart-control-sc-1000-knx/smart-control-sc-1000-knx_product-documentation_2031686052.webp)
Art. No. SC 1000 KNX
Function:
Channel function "Dimming (Brightness value)"
Object
h
135
Function
Dimming (Brightness value)
Name
D.Output
Channel 1
1
Type
1 byte
DPT
5.001
Flag
C, W, T,
(R)
2
Description
1-bit object for transmitting brightness value telegrams (0...255) if the sensor
element is touched. This can cause a dimmer actuator to be activated.
The transmitted decimal data values 0...255 must be evaluated by the actuator
as percentages 0...100 %.
Function:
Channel function "Dimming (Brightness value)"
Object
h
137
Function
Dimming Feedb. Brightness
value
Name
D.Output
Channel 1
1
Type
1 byte
DPT
5.001
Flag
C, W, T,
(R)
2
Description
1-byte object for receiving brightness value telegrams that a dimmer actuator
transmits, for example. The status value, status icon and bar graph are
influenced as a result. The feedback of the brightness value must be
transmitted by the "actively transmitting" actuator. If the activated KNX dimmer
actuator does not have a separate brightness value feedback, this object can
be linked with the object "D.Output channel x - dimming (brightness value)" via
an identical group address.
The decimal data values 0...255 are evaluated as percentages 0...100 %.
Function:
Channel function "Venetian blind (Step/Move/Step)
Object
h
135
Function
Venetian blind (Step)
Name
D.Output
Channel 1
1
Type
1-bit
DPT
1.007
Flag
C, -, T, (R)
2
Description
1-bit object for the transmission of telegrams with which a Venetian blind or
shutter drive motor can be stopped or the blind slats can be adjusted by short
time operation after a short touch of the sensor element.
Function:
Channel function "Venetian blind (Step/Move/Step)
Object
h
136
Function
Venetian blind (Move)
Name
D.Output
Channel 1
1
Type
1-bit
DPT
1.008
Flag
C, W, T,
(R)
2
Description
1-bit object for the transmission of telegrams with which a Venetian blind or
shutter drive motor can be can be moved upwards or downwards after a long
press of the sensor element.
1: The objects have been described for channel 1 as an example. The objects for the other
channels are defined in the same way by shifting the object number and changing the object
name.
2: For reading, the R-flag must be set. The last value written to the object via the bus or by the
device will be read.
Page 52 of 347