Art. No. SC 1000 KNX
The standby and night set-temperatures are derived after the configured increase temperatures
from the comfort set-temperature (basic setpoint).
The heat protection is supposed to ensure that the temperature does not exceed the maximum
permissible room temperature in order to protect system components. For this reason, the heat
protection temperature should be set to a larger value than the night temperature
(default: +35 °C). In principle, however, it is possible to select heat protection temperature
values b7 °C and +45 °C.
The possible range of values for a setpoint temperature lies between -99.9 °C and +45.0 °C for
"cooling" and is bounded by the heat protection temperature in the upper range.
The level offset configured in ETS will be additionally considered in a two-level cooling mode
(figure 102).
Figure 102: Setpoint temperatures in the operating mode "Basic and additional cooling"
(recommended specification)
T
Comfort setpoint basic level heating
≤ T
Comfort setpoint additional level heating
T
Standby setpoint basic level heating
≤ T
Standby setpoint additional level heating
T
Comfort setpoint cooling
≤ T
Standby setpoint cooling
or
T
Comfort setpoint basic level heating
≤ T
Comfort setpoint additional level heating
T
Night setpoint basic level heating
≤ T
Night setpoint additional level heating
T
Comfort setpoint cooling
≤ T
Night setpoint cooling
Page 192 of 347